ATEX |
/KU2 |
4-20mA:
[Intrinsically safe approval]
Applicable Standard: EN 60079-0: 2012+A11:2013, EN 60079-11: 2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T5..T4 Ga
Ambient Temperature: -40 to 70°C for T4, -40 to 50°C for T5
Enclosure: IP66/IP67 in accordance with only IEC 60529
Entity Parameters:
Supply/Output circuit: Ui=30V, li=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s, 1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
Certificate: KEMA 07ATEX0130
II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: -40 to 75°C for T6, -40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: -30 to 65°C for T70°C, -30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female(1) |