IECEx |
/SU2 |
4-20mA:
[Intrinsically safe ia, ic pproval]
Applicable Standard: IEC 60079-0, IEC 60079-11
Certificate No. IECEx FMG 16.0014X
Ex ia IIC T5…T4 Ga
Ex ic IIC T5…T4 Gc
Ex ia [ia Da] IIIC T135°C Db
Ambient Temperature:
–40 to +70°C for T4 (Ex ia), –40 to +50°C for T5 (Ex ia), –30 to +70°C for IIIC (Ex ia),
–30 to +70°C for T4 (Ex ic), –30 to +50°C for T5 (Ex ic)
Enclosure: IP66/IP67
Over voltage category: I
Electrical parameters (Ex ia)
Supply/Output circuit: Terminal: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Electrical parameters (Ex ic)
Supply/Output circuit: Terminal: +, –
Ui=30V, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Applicable standard: IEC 60079-0, IEC 60079-1, IEC 60079-31
Certificate: IECEx KEM 07.0044X
Ex db IIC T6/T5 Gb, Ex tb IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C (–40 to 167°F) for T6,
–40 to 80°C (–40 to 176°F) for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C (–22 to 149°F) for T70°C,
–30 to 80°C (–22 to 176°F) for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female² |