YTA610-JA1C4DN/N4/FU1+DOCTC | Yokogawa YTA610 | Yokogawa Temperature Transmitter

Part Number: YTA610-JA1C4DN/N4/FU1+DOCTC

  • Free Selection Free Online Product Selection Service

To pick up today

  • Fast Shipping & Competitive pricing

Our courier will deliver to the specified address

  • warranty Min. order: 1 piece & 2-Year Warranty

DHL courier will deliver to the specified address

Payment Methods:

Description

Part Number: YTA610-JA1C4DN/N4/FU1+DOCTC

Model: YTA610 Temperature Transmitter
Brand: Yokogawa
Condition: New & Original in Factory Packing
Factory Warranty: 12 Months

Ordering Information

Model YTA610 Temperature Transmitter
Output Signal -J 4 to 20 mA DC with digital communication HART protocol
A Alway A (Global)
Sensor Input 1 Single
Housing Code C Stainless
Electrical Connection 4 M20 female
Integral Indicator D Digital indicator with local operating switch
Mounting bracket N None
Wired tag plate /N4 SUS316 stainless steel tag plate wired onto transmitter
FM (US) /FU1 4-20mA:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: Class 3600:2011, Class 3610:2015, Class 3611:2004, Class 3810:2005,
ANSI/ISA-60079-0:2013, ANSI/ISA-60079-11:2014, NEMA 250:2003, ANSI/IEC 60529:2004 (R2011)
Intrinsically safe for
Class I, II, III Division 1, Groups A, B, C, D, E, F, G, T5…T4
Class I Zone 0 AEx ia IIC T5…T4
Non-incendive for
Class I, II, Division II, Groups A, B, C, D, F, G, T5…T4
Class III, Division 1 T5…T4
Class I Zone 2 Group IIC T5…T4
Ambient Temperature: -40 to 70°C for T4, -40 to 50°C for T5
Enclosure Type 4X, IP66/IP67 in accordance with only IEC 60529
Entity Parameters:
Intrinsically safe for
Supply/Output circuit: Ui=30V, li=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Ui=30V, Ci=22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s., 1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
[Explosionproof approval]
Applicable standard: Class 3600, Class 3615, Class 3810, ANSI/NEMA250
Class I, Division 1, Groups A, B, C and D.;
Class II,III, Division 1, Groups E, F and G.
‘FACTORY SEALED, CONDUIT SEAL NOT REQUIRED’
Enclosure Ratings: TYPE 4X
Temperature Class: T6
Ambient Temperature: -40 to 60°C (-40 to 140°F)
Electrical Connection: 1/2NPT female¹
+DOCTC
  1. Applicable for Electrical Connection Code 2.
  • Estimated Lead Time: 6 – 7 Months
  • Shipping Weight: 10 Kg